Splitter attenuator type MSA with integrated splitters type MKA.
The splitter frame with flow-optimised profile reduces the pressure drop in comparison to conventional splitters by up to 30 %. This enables high energy savings when operating air conditioning systems.
- Splitter attenuator efficient according to the chamber absorption principle
- Aerodynamically shaped frame of galvanised sheet steel, stiffened by crimping
- Absorption material (highly biodegradable, no health risk) with laminated non-woven glass fibre fabric to provide protection against abrasion at air velocities of up to 20 m/s; rot-proof and moisture-repellent impregnation, non-flammable according to DIN 4102 A2
- External lambda panels and internal partitioning panels of galvanised sheet steel
Splitter attenuator type MSA, incorporating type MKA splitters operates according to the chamber absorption principle. The special design causes an increased insertion loss in the area of fan noises compared to real absorption splitters.
Splitters and splitter attenuators are suitable for use in air conditioning and ventilation systems certified and compliant to VDI 6022 Part 1 and Part 3 as well as to DIN 1946 Part 2 and Part 4 and VDI 3803.
The turbulences of the sound attenuator inlet and outlet are reduced by the aerodynamically profiled frame of the splitters. The pressure drop is reduced up to 30 %.
It is thus possible to select smaller gaps and a shorter silencer.
As a result, a more compact design results in direct savings of the operating costs and/or in space saving. When using additional necessary aerodynamic profiles, acoustic and ineffective splitters lengths can be avoided.
Casing
- Folded casing of galvanised sheet steel stiffened by crimping; larger dimensions additionally with reinforcing strip.
- Connection frame air duct section (30 mm); alternatively, a frame perforated at the factory of galvanised angular steel 35 by 5 mm available.
Splitters
- Aerodynamically shaped frame of galvanised sheet steel, stiffened by crimping.
- Absorption material (highly bio-degradable, no health risk) with laminated non-woven glass fibre fabric to provide protection against abrasion at air velocities of up to 20 m/s; rot-proof and moisture-repellent impregnation, non-flammable according to DIN 4102 A2.
- External lambda panels and internal partitioning panels of galvanised sheet steel.
- Operating temperature up to 100 °C.
- Can be installed in any position up to a height of and including 1200 mm.
- Fulfills the hygiene requirements of VDI 6022, DIN 1946 part 2 and part 4 as well as of VDI 3803.
| Downloads |
Group |
Type |
Ident-No. |
Type / Size |
| |
|
|
|
|
| MSA · MKA |
Splitter Attenuators |
Technical Leaflet |
6/9/EN/2 |
PDF / 227 KB |
| VDI 6022 for MSA, XSA |
Splitter Attenuators |
|
PM 2007 |
PDF / 235 KB |
Reference
Schalke-Arena
One trusts in TROX attenuation also „On Schalke“.
Reference
Contact
TROX GmbH
Heinrich-Trox-Platz
D-47504 Neukirchen-Vluyn
Tel.: +49 (0)2845 / 202-0
Contact and locations