search-loading


VARYCONTROL


Air terminal units for supply or extract air for a variety of applications

Units of the VARYCONTROL types are air terminal units for supply and extract air systems. They can be used for almost any control, regulation and shut-off tasks in room air conditioning systems. The selection of the type of units is based on the acoustical requirements and the control functions.

Type TVZ · TVA

TVZ
  • Air terminal unit
  • Airtight shut-off
  • Flow rate control or duct or room pressure control
  • Electronic or pneumatic control components
  • Hygienically tested and certified according to VDI 6022


more details

circular, rectangular

15 – 1,680 l/s
54 – 6,048 m³/h
32 – 3,560 cfm
Δp: 20 – 1,500 Pa

Ø 125 – 400 mm

Casing air leakage flow rate complies with DIN EN 1751, class A
Control damper closed blade leakage complies with DIN EN 1751, class 4 (nominal size 125, class 3)

Type TVM

TVM
  • Dual duct air terminal unit
  • Airtight shut-off
  • Flow rate control
  • Electronic or pneumatic control components
  • Hygienically tested and certified according to VDI 6022


more details

circular, rectangular

45 – 1,680 l/s
162 – 6,048 m³/h
95 – 3,560 cfm
Δp: 150 – 1,500 Pa

Ø 125 – 400 mm

Casing air leakage flow rate complies with DIN EN 1751, class A
Control damper closed blade leakage complies with DIN EN 1751, class 4 (nominal size 125, class 3)

Type TVZ-Easy ·
TVA-Easy

TVZ-Easy
  • Easy - the innovative solution
  • Air terminal unit
  • Airtight shut-off
  • Flow rate control
  • Hygienically tested and certified according to VDI 6022


more details

circular, rectangular

15 – 1,675 l/s
54 – 6,030 m³/h
32 – 3,549 cfm
Δp: 20 – 1,000 Pa

Ø 125 – 400 mm

Casing air leakage flow rate complies with DIN EN 1751, class A
Control damper closed blade leakage complies with DIN EN 1751, class 4 (nominal size 125, class 3)

Type TVR

TVR
  • Circular vav controller
  • Airtight shut-off
  • Flow rate control or duct or room pressure control
  • Electronic or pneumatic control components


more details

circular

10 – 1,680 l/s
54 – 6,048 m³/h
21 – 3,560 cfm
Δp: 20 – 1,500 Pa

Ø 100 – 400 mm

Casing air leakage flow rate complies with DIN EN 1751, class A
Control damper closed blade leakage complies with DIN EN 1751, class 4 (nominal size 100 and 125, class 3)

Type TVJ · TVT

TVT
  • Rectangular vav controller
  • Airtight shut-off
  • Flow rate control or duct or room pressure control
  • Electronic or pneumatic control components


more details

square, rectangular

45 – 10,100 l/s
162 – 36,360 m³/h
95 – 21,401 cfm
Δp: 20 – 1,000 Pa

W: 200 – 1,000 mm
H: 100 – 1,000 mm

Casing air leakage flow rate complies with DIN EN 1751, class A
Control damper closed blade leakage complies with DIN EN 1751,
TVT: class 4 (B < 600, class 3)
TVJ: class 1 (H = 100, class 0)

Type TVRK

TVRK
  • Circular plastic vav controller
  • Airtight shut-off
  • Flow rate control or duct or room pressure control
  • Electronic or pneumatic control components


more details

circular

30 – 1,025 l/s
108 – 3,690 m³/h
64 – 2,172 cfm
Δp: 20 – 1,500 Pa

Ø 125 – 315 mm

Casing air leakage flow rate complies with DIN EN 1751, class A
Control damper closed blade leakage complies with DIN EN 1751, class 4 (nominal size 125, class 3)

Type TVR-Easy

TVR-Easy 160
  • Easy - the innovative solution
  • Circular vav-controller
  • Airtight shut-off
  • Flow rate control


more details

circular

10 – 1,675 l/s
36 – 6,030 m³/h
23 – 3,549 cfm
Δp: 20 – 1,000 Pa

Ø 100 – 400 mm

Casing air leakage flow rate complies with DIN EN 1751, class A
Control damper closed blade leakage complies with DIN EN 1751, class 4 (nominal size 100 and 125, class 3)

Type TVJ-Easy ·
TVT-Easy

TVJ EASY
  • Easy - the innovative solution
  • Rectangular vav-controller
  • Airtight shut-off (Not for TVJ)
  • Flow rate control


more details

square, rectangular

35 – 10,455 l/s
126 – 37,638 m³/h
74 – 22,153 cfm
Δp: 20 – 1,000 Pa

W: 200 – 1,000 mm
H: 100 – 1,000 mm

Casing air leakage flow rate complies with DIN EN 1751, class A
Control damper closed blade leakage complies with DIN EN 1751,
TVT-Easy: class 4 (B < 600, class 3)
TVJ-Easy: class 1 (H = 100, class 0)

Type WT · WL · EL

WT
  • Air Heater
  • Hot water for types TVZ, TVR, TVJ, TVT, RN and EN
  • Electric for types TVR and RN
  • Installation, heating output control and the supply connections are provided by customer

more details

circular, square, rectangular

10 – 10.100 l/s
36 – 36.360 m³/h
21 – 21.401 cfm

Ø 100 – 400 mm
B: 200 – 1.000 mm
H: 100 – 1.000 mm

Q: 0,25 – 116 kW

Control Components