Type VFR


TROX type VFR dampers are used to adjust volume flow rates in air-conditioning and ventilation systems. They can be used in circular ventilation ducts with nominal sizes 80 to 250 and system pressures up to 1000 Pa.

VFR
VFR - man
VFR - E0..
VFR - M0..
  • Circular damper
  • Flow rate balancing based on network calculation
  • Every balancing damper has a diagram
  • Adjustment of duct pressure possible
  • Manual operation or electric actuator
  • Easy retrofit of an actuator is also possible

The damper blade is designed without a seal and with a circumferential gap between the case and blade tip of approximately 3 mm.

For the flow rate balancing the lockable hand wheel is steplessly adjustable over a scale range of 0 to 10. For site set up the required set point as a function of pressure difference and flow rate is indicated on a diagram label affixed to the outside casing of each VFR.

At the minimum setting (closed position 0) a system pressure dependent leakage flow rate occurs. Hence for low leakage shut-off of ducts according to EN 1751 type AK shut-off dampers must be used. See leaflet no. 5/10/EN/...

Min/max changeover is possible with VFR dampers equipped with an electric actuator. Easy retrofit of an actuator is also possible.

Downloads Group Type Ident-No. Type / Size
         
VFR Balancing dampers Technical Leaflet 5/10.3/EN/2 PDF / 256 KB