Active chilled beams Type DID604 using air-water systems provide a comfortable air conditioning of rooms with a high cooling load. They combine the aerodynamic properties of ceiling diffusers with the energy benefits of load dissipation using water.

Due to its low height construction, Type DID604 is particularly suited for low false ceiling voids in new buildings and for the refurbishment of existing buildings with clear room heights of approximately 2.6 m to 4.0 m.

DID604
  • Flush ceiling active chilled beam
  • Nominal width size 600 mm
  • High cooling capacity with low conditioned fresh air flow rates, low air velocities in the occupied zone and low sound power levels
  • Adjustable control blades to control the air discharge direction
  • Air discharge four way
  • Vertically mounted heat exchangers with condensate drip trays for low chilled water flow temperatures
  • Heat exchangers for two or four pipe systems
  • Heating and/or cooling is possible

DID604
Active chilled beams supply conditioned fresh air (primary air) to the space from a central plant room to maintain indoor air quality whilst providing additional cooling and/or heating using heat exchangers.

The primary air is discharged into the beam mixing chamber via nozzles. As a result of this secondary air is induced via an inlet grille and then passes through a vertically mounted heat exchanger into the mixing chamber. Both air flows mix and the total supply air is discharged horizontally into the space through four integral slot diffusers.

There are two nominal sizes each having three nozzle options. This allows the optimum selection to meet fresh air flow rate and thermal capacity requirements whilst exhibiting low differential pressures and sound power level characteristics.

There are two types of heat exchanger, one is a two pipe system for cooling, heating can be provided using a changeover mode. The other is a four pipe system which enables any room to be cooled or heated independently of other rooms.

A condensate drip tray is located beneath the heat exchanger to collect any condensate resulting from undershooting the dew point temperature in the cooling mode. Long-term operation below the dew point (wet operation) must be avoided.

 

Downloads Group Type Ident-No. Type / Size
         
DID604 Active Chilled Beams Technical Leaflet T 2.4/10/EN/2 PDF / 709 KB 

Reference

Distrito de la Comunicación de Telefónica

More than 30,000 TROX chilled beams of DID300B type
Reference

Contact

TROX GmbH

Heinrich-Trox-Platz
D-47504 Neukirchen-Vluyn
Tel.: +49 (0)2845 / 202-0
Contact and locations