search-loading

Type DID312


Active chilled beams Type DID312 for air-water systems permits a comfortable air conditioning of rooms with a high cooling load. The flow characteristics of ceiling diffusers and the energetic advantages of water as a medium for load dissipation are optimally used.

Due to its flat construction, Type DID312 is particularly suited for low false ceilings in new buildings and for the refurbishment of existing buildings with clear room heights of 2.60 – 4.00 m.

DID312_240
DID312-LR / DID312-LQ_240
DID312-GL / DID312-GQ_240
  • Flush ceiling active chilled beam
  • Nominal width 300 mm
  • Four options of induced air grille design
  • Heat exchanger vertically mounted with condensate drip tray for low chilled water temperatures
  • Side entry spigot for fresh air
  • Supply-extract-air combination available

DID312_Schnitt_240
Active chilled beams supply fresh air to the space from a central plant room to maintain indoor air quality whilst providing additional cooling and/or heating using heat exchangers.
The fresh air is discharged into the beam mixing chambers via nozzles. As a result of this secondary air is induced via an inlet grille and then passes through vertically mounted heat exchangers into the mixing chambers. Here it is mixed with the fresh air and the total supply air is discharged horizontally into the space through integral slot diffusers.
The selection of eight nominal lengths combined with three nozzle sizes each permits an optimum adaptation to the required outside air flow rate and the thermal output, at low sound power and low differential pressure.
Heat exchangers are available in two variants.With the two pipe system, cooling is possible, while heating is possible in changeover mode. The four pipe systems lets any room be heated or cooled at any time independently of other rooms. Condensate drip trays that take up any condensate produced in case the dew point is undershot in cooling mode are located underneath the heat exchangers. Long-term operation under the dew point (wet operation) must be avoided.

 

Downloads Group Type Ident-No. Type / Size
         
DID312 Active Chilled Beams Technical Leaflet T 2.4/1/EN/1 PDF / 1.0 MB 

Reference

Distrito de la Comunicación de Telefónica

More than 30,000 TROX chilled beams of DID300B type
Reference

Contact

TROX GmbH

Heinrich-Trox-Platz
D-47504 Neukirchen-Vluyn
Tel.: +49 (0)2845 / 202-0
Contact and locations